Duplex Lift Station Control Panel
Motor Circuit Protector

The Magnetic Circuit Protector (MCP) provides an instantaneous trip in the event of a short circuit or a locked rotor condition. This offers improved protection for the motor starter, wiring, and motor over standard circuit breakers. The ampacity is fixed at 50 amps and the magnetic trip setting is adjustable over a range of 150 to 550 amps. The setting used is relative to the full load amperage of the motors and is given in the table at right.

Motor overload protection is handled by the motor starter.

Trip
Setting
Motor FLA
MCP Trip
Amperes
A
11.5 - 15.2
150
B
19.2 - 22.9
250
C
26.9 - 30.6
350
D
34.6 - 38.3
450
E
38.4 - 42.1
500
F
42.2 - 43.5
550
Return to Duplex Lift Station Control Panel Return to Start