| 2 Pump | 2 Pump | 2 Pump | 2 Pump | 2 Pump |
| Starter & Motor Circuit Breaker Included | Starter & Motor Circuit Breaker Included | Starter & Motor Circuit Breaker Included | Starter & Motor Circuit Breaker Included | Starter & Motor Circuit Breaker Included |
Starter/Breaker Type | IEC Rated | IEC Rated | IEC Rated Option: Nema | IEC Rated Option: Nema | IEC Rated Option: Nema |
Pump Power Supply | Single Phase Option: 3-Phase | Single Phase Option: 3-Phase | Single Phase Option: 3-Phase | Single Phase Option: 3-Phase | Single Phase Option: 3-Phase |
Single Phase IEC Pump Rating | 115Vac = 2HP 230Vac = 5HP | 115Vac = 2HP 230Vac = 5HP | 115Vac = 2HP 230Vac = 5HP | 115Vac = 2HP 230Vac = 5HP | 115Vac = 2HP 230Vac = 5HP |
Three Phase IEC Pump Rating | 230Vac = 2 HP 460Vac = 20HP | 230Vac = 2 HP 460Vac = 20HP | 230Vac = 2 HP 460Vac = 20HP | 230Vac = 2 HP 460Vac = 20HP | 230Vac = 2 HP 460Vac = 20HP |
Panel | FRP Nema 4X 24" x 20" | FRP Nema 4X 24" x 20" | FRP Nema 4X 30" x 24" | FRP Nema 4X 36" x 30" | FRP Nema 4X 36" x 30" |
Operator Interface Console (OIC) | Color Touch Screen - Internal or "Through Door" Mounting | Color Touch Screen - Internal or "Through Door" Mounting | Color Touch Screen - Internal or "Through Door" Mounting | Color Touch Screen - Internal or "Through Door" Mounting | Color Touch Screen - Internal or "Through Door" Mounting |
Programmable Logic Controller (PLC) | 2 Individual - Autodialer Not Included | 4 Individual - Autodialer Not Included | 4 Individual - Autodialer Not Included | 4 Individual - Autodialer Not Included | 4 Individual - Autodialer Not Included |
Remote Communications | Option: Local DH485 Net | Option: Additional RS232 Serial Port (1764-LRP) | Option: Additional RS232 Serial Port (1764-LRP) | Option: Additional RS232 Serial Port (1764-LRP) | Option: Additional RS232 Serial Port (1764-LRP) |
Type Of Remote Comm | PC Screen within 8,000ft | Radio or Phone Telemetry | Radio or Phone Telemetry | Radio or Phone Telemetry | Radio or Phone Telemetry |
Lightning Protection | Inputs & Outputs Isolated Except Autodialer Outputs | Inputs & Outputs Isolated Except Autodialer Outputs | Inputs & Outputs Isolated Except Autodialer Outputs | Inputs & Outputs Isolated Except Autodialer Outputs | Inputs & Outputs Isolated Except Autodialer Outputs |
Control Power | 120Vac - UPS Recommended | 120Vac - UPS Recommended | 120Vac - UPS Recommended | 120Vac - UPS Recommended | 120Vac - UPS Recommended |
Manual Operation | Inputs & Outputs Are Controlled Through Hand-Off-Auto Switches Except for Autodialer | Inputs & Outputs Are Controlled Through Hand-Off-Auto Switches Except for Autodialer | Inputs & Outputs Are Controlled Through Hand-Off-Auto Switches Except for Autodialer | Inputs & Outputs Are Controlled Through Hand-Off-Auto Switches Except for Autodialer | Inputs & Outputs Are Controlled Through Hand-Off-Auto Switches Except for Autodialer |
Wetwell (Storage Tank) | Five Float Auto Operating System: Low Level Pump Off Pump Enable High Duty High Level | Five Float Auto Operating System: Low Level Pump Off Pump Enable High Duty High Level | Five Float Auto Operating System: Low Level Pump Off Pump Enable High Duty High Level | Five Float Auto Operating System: Low Level Pump Off Pump Enable High Duty High Level | Five Float Auto Operating System: Low Level Pump Off Pump Enable High Duty High Level |
Zones | Automatic Zone Dosing Based on Time or Flow; Automatic Field Flush (7-30 Days) | Automatic Zone Dosing Based on Time or Flow; Automatic Field Flush (7-30 Days) | Automatic Zone Dosing Based on Time or Flow; Automatic Field Flush (7-30 Days) | Automatic Zone Dosing Based on Time or Flow; Automatic Field Flush (7-30 Days) | Automatic Zone Dosing Based on Time or Flow; Automatic Field Flush (7-30 Days) |
Filters | Automatic Filter Backwash & Air Scour Based on Back-Pressure, Dosing Time or Manual Initiation | Automatic Filter Backwash & Air Scour Based on Back-Pressure, Dosing Time or Manual Initiation | Automatic Filter Backwash & Air Scour Based on Back-Pressure, Dosing Time or Manual Initiation | Automatic Filter Backwash & Air Scour Based on Back-Pressure, Dosing Time or Manual Initiation | Automatic Filter Backwash & Air Scour Based on Back-Pressure, Dosing Time or Manual Initiation |
Single Contingency Failure Protection Logic | Float Failure Pump Failure Zone Failure | Float Failure Pump Failure Zone Failure | Float Failure Pump Failure Zone Failure | Float Failure Pump Failure Zone Failure | Float Failure Pump Failure Zone Failure |